漏水測(cè)試
完工的屋面和壁板安裝應(yīng)絕對(duì)沒(méi)有水泄漏的現(xiàn)象。 雇主保留在安裝過(guò)程中隨時(shí)對(duì)屋面和壁板進(jìn)行漏水測(cè)試的權(quán)利。
在這種水泄露測(cè)試中,應(yīng)發(fā)現(xiàn)任何可能存在的水泄露。 屋面和/或壁板應(yīng)根據(jù)雇主的指示拆開(kāi),接頭應(yīng)用指定的密封膠或膠帶重新密封,重新安裝屋面和/或壁板。 接頭應(yīng)安裝雇主的指示對(duì)所有隨后的面板進(jìn)行密封。

保修
安裝驗(yàn)收后,投標(biāo)人應(yīng)提供一份書(shū)面保修給業(yè)主,保證氟碳涂層依照持牌制造商過(guò)程指示并符合下列標(biāo)準(zhǔn),在正常條件使用最低10年。(投標(biāo)人應(yīng)說(shuō)明保修年數(shù)和免費(fèi)更換有缺陷

面板的次數(shù)):
粉化不會(huì)超過(guò)ASTM D659 No. 8級(jí)。 粉化級(jí)別應(yīng)取決于ASTM D659概述的程序。
依照ASTM D2244 規(guī)定的標(biāo)準(zhǔn),去除外部沉積和粉化,色差不會(huì)超過(guò)5個(gè)NBS單位。
不會(huì)
目錄
第三冊(cè)
第4.4部分  土建工程
4.4.3.24 其他建筑工程.....................................................................................................270
  4.4.3.24.1 工程范圍...........................................................................................270
  4.4.3.24.2 規(guī)范與標(biāo)準(zhǔn).......................................................................................271
  4.4.3.24.3 門(mén)......................................................................................................271
  4.4.3.24.4 窗......................................................................................................278
  4.4.3.24.5 百葉窗..............................................................................................281
  4.4.3.24.6 地面工程...........................................................................................283
  4.4.3.24.7 石方工程...........................................................................................289
  4.4.3.24.8 天花板工程.......................................................................................294
  4.4.3.24.9 水管..................................................................................................296
  4.4.3.24.10 天棚................................................................................................314
  4.4.3.24.11 木工工程.........................................................................................316
  4.4.3.24.12 建筑用具和專(zhuān)業(yè)用具.......................................................................318
4.4.3.24其他建筑工程
4.4.3.24.1工程范圍  
  其他建筑工程應(yīng)包括投標(biāo)人對(duì)本規(guī)范所涵蓋的下列工程的設(shè)計(jì)、詳細(xì)說(shuō)明、家具、安裝檢驗(yàn)和測(cè)試,適用于投標(biāo)人的建設(shè)工作參見(jiàn)“工程概述”,技術(shù)規(guī)格參見(jiàn)

“通用土建和建筑設(shè)計(jì)的要求”。 所有材料和施工應(yīng)保持整潔,須獲得業(yè)主的事先批準(zhǔn)并執(zhí)行最佳的現(xiàn)代實(shí)踐。

門(mén)
- 中空金屬門(mén)
- 鋼卷門(mén)
- 鋁制門(mén)

- 鋁制上懸窗
- 鋁制平移窗
- 鋁制固定窗
百葉窗
- 固定百葉窗
地面工程
- 整體修整
- 混凝土地面單獨(dú)修整
- 陶瓷
石方工程
- 砌磚工程
- 抹灰工程
天花板工程
- 天花板方格
- 吸聲天花板
水管
- 地面排水管
- 屋面排水管
- 下水管道裝置
  天棚
  木工工程
  建筑用具
- 廚房成套家具
- 鋼儲(chǔ)物柜
4.4.3.24.2規(guī)范與標(biāo)準(zhǔn)
  摘自“規(guī)范和標(biāo)準(zhǔn)”中下列組織制定的規(guī)范和標(biāo)準(zhǔn)特別適用于本規(guī)范的設(shè)計(jì)、制造和測(cè)試工作:
AA 美國(guó)鋁業(yè)協(xié)會(huì)
AAMA 美國(guó)建筑門(mén)窗工業(yè)協(xié)會(huì)
ACI 美國(guó)混凝土學(xué)會(huì)
AMCA 美國(guó)通風(fēng)與空調(diào)協(xié)會(huì)
ANSI 美國(guó)國(guó)家標(biāo)準(zhǔn)學(xué)會(huì)
ASTM 美國(guó)材料與試驗(yàn)協(xié)會(huì)
AWWA 美國(guó)用水工業(yè)協(xié)會(huì)
LIA 美國(guó)鉛工業(yè)協(xié)會(huì)
JIS 日本工業(yè)標(biāo)準(zhǔn)
NAAMM 美國(guó)建筑用金屬制造商協(xié)會(huì)
NEMA 美國(guó)電氣制造商協(xié)會(huì)
NFPA 美國(guó)消防協(xié)會(huì)
SSPC 美國(guó)防護(hù)涂料協(xié)會(huì)
UL 美國(guó)保險(xiǎn)商實(shí)驗(yàn)室協(xié)會(huì)
N.1.5. Peraturan konstruksi kayu indonesia (印尼木結(jié)構(gòu)規(guī)例)
N.J.10. Bata merah sebagai bahangangunan (印尼磚標(biāo)準(zhǔn))
ICE 國(guó)際電工委員會(huì)
4.4.3.24.3門(mén)
  概述
  投標(biāo)者設(shè)計(jì)和提供的所有門(mén)應(yīng)滿(mǎn)足以下最低要求:
  設(shè)計(jì)荷載
  風(fēng)荷載
  外部門(mén)的設(shè)計(jì)應(yīng)能承受150 kg/m2最低風(fēng)壓,室內(nèi)門(mén)應(yīng)能承受100 kg/ m2最低風(fēng)壓;該標(biāo)準(zhǔn)一律適用于大門(mén)的整個(gè)區(qū)域。
受到風(fēng)力的大門(mén)最大撓度應(yīng)達(dá)到寬度跨度的1/120。
操作負(fù)荷
所有外部門(mén)的設(shè)計(jì)應(yīng)能在50 kg/m2的最低載荷下正常使用,一律適用于大門(mén)的整個(gè)區(qū)域。
  推拉中空金屬門(mén)
  中空金屬門(mén)的使用
I類(lèi)門(mén)
無(wú)縫空心鋼結(jié)構(gòu)建筑,與1.5875毫米面板和額外的管型加固、鉸式門(mén)窗邊框和鎖具或推拉配件,并準(zhǔn)備表面鉸鏈,除非另有說(shuō)明。
I類(lèi)門(mén)應(yīng)適用于所有外部門(mén)的位置。I類(lèi)門(mén)也可用于暴露在交通繁忙地區(qū)的室內(nèi)門(mén)、濫用的大門(mén)和具有極端室內(nèi)外溫差的大門(mén)。
  II類(lèi)門(mén)
無(wú)縫空心鋼結(jié)構(gòu)建筑,與1.27毫米面板和額外的管型加固,準(zhǔn)備開(kāi)榫鉸接,除非另有說(shuō)明。II類(lèi)門(mén)是在門(mén)關(guān)閉位置。
中空金屬門(mén)
該類(lèi)型的門(mén)應(yīng)采用嵌入式。 為了安全或順利操作應(yīng)使用觀察窗,即:在大門(mén)處于關(guān)閉狀態(tài)時(shí)通過(guò)觀察窗查看門(mén)的另一邊發(fā)生了什么。
  材料 
面板應(yīng)碾壓平整,采用優(yōu)質(zhì)冷軋?zhí)间摗?br />   加勁肋、加固件和其他配件,應(yīng)采用優(yōu)質(zhì)碳素鋼。
  玻璃
a. 玻璃裝配應(yīng)符合ANSI Z97.1的要求。
b. 普通的大門(mén)玻璃應(yīng)包括至少為6毫米厚的拋光線鋼筋玻璃。
c. 鑲玻璃材料應(yīng)依照制造商的建議。
d. 調(diào)整塊和調(diào)整墊片應(yīng)采用氯丁橡膠制造,并應(yīng)根據(jù)玻璃制造商的建議提供。
門(mén)框
中空金屬門(mén)門(mén)框應(yīng)采用槽鋼門(mén)框(ASTM A36)或壓型金屬門(mén)框(優(yōu)質(zhì)冷軋?zhí)间?。 凡是要求具有防火門(mén)時(shí),應(yīng)使用門(mén)框結(jié)構(gòu)。
硬件
大門(mén)的硬件應(yīng)包括鎖、拉手、閉合器、門(mén)吸、逃生門(mén)推桿鎖等。該緊固件應(yīng)采用304型不銹鋼用于外部門(mén),黃銅用于室內(nèi)門(mén)。所有的硬件應(yīng)符合業(yè)主的事先批準(zhǔn)。
大門(mén)施工細(xì)節(jié)
總則
a. 所有的大門(mén)應(yīng)遵照ANSI A123.1采用無(wú)縫空心鋼結(jié)構(gòu),每個(gè)大門(mén)采用兩塊面鋼構(gòu)成。 大門(mén)表面或側(cè)面部應(yīng)出現(xiàn)裂縫。 大門(mén)的頂部和底部應(yīng)封閉,內(nèi)部結(jié)構(gòu)應(yīng)采用鋼加勁肋

組成。
b. 所有為空調(diào)房間提供的大門(mén)每立方米密度應(yīng)采用48.00 kg的纖維玻璃或礦棉,并且保險(xiǎn)商實(shí)驗(yàn)室協(xié)會(huì)認(rèn)證該服務(wù)。
大門(mén)細(xì)節(jié)
a. 底部?jī)艟?nbsp;:大門(mén)底部和地面之間應(yīng)最高3毫米。
b. 對(duì)于具有榫眼的大門(mén) :大門(mén)和門(mén)框應(yīng)開(kāi)榫眼。
c. 底部滴水 :所有大門(mén)應(yīng)提供。
d. 裝飾鑲條 :所有大門(mén)的活動(dòng)葉片應(yīng)提供。
e. 門(mén)窗密封條 :所有大門(mén)應(yīng)提供。
f. 玻璃細(xì)節(jié) :外部門(mén)應(yīng)提供固定玻璃,大門(mén)的內(nèi)側(cè)應(yīng)提供可移動(dòng)的鑲玻璃條。
WATER TESTING
The completed roofing and siding installation shall be such that absolutely no water shall leak through. The Employer reserves the right to conduct water leakage tests on installed roofing and siding at any time during the installation.
Should any leakage be discovered during such leakage test. The roofing and/or siding shall disassemble to the extent directed by the Employer and joints shall be resealed with specified sealant or tape, and the roofing, and/or siding reinstalled. Joints shall be sealed as directed by the Employer on all subsequent panels.
Warranty
The Bidder shall furnish the Owner, upon acceptance installation, a written warranty that fluorocarbon organic coating has been applied in accordance with licensee manufacturers process instructions and under normal conditions; and it shall meet the following standards for a minimum period of 10 years (the Bidder shall state the number of years warranty and also the number of times he will replace any defective panels without charges of any kind):
Will not chalk in excess of ASTM D659 No. 8 rating. Chalk rating shall be determined by the procedure outlined in ASTM D659.
Will not change colour more than 5 NBS units as determined in accordance with procedures set forth in ASTM D 2244, after removal of external deposits and chalk.
Will not crack, check or peel (lose adhesion).
0310295
Revision 0 Part 4.4 - 269 PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
BOOK III
PART 4.4. Civil Works 4.4.3 Technical Specification
TABLE OF CONTENT
BOOK III PART 4.4   CIVIL WORKS
4.4.3.24     MISCELLANEOUS ARCHITECTURAL WORK 270
4.4.3.24.1 SCOPE OF WORK 270
4.4.3.24.2 CODES AND STANDARDS 271
4.4.3.24.3 DOORS 271
4.4.3.24.4 WINDOWS 278
4.4.3.24.5 LOUVERS 281
4.4.3.24.6 FLOOR FINISH 283
4.4.3.24.7 MASONRY WORK 289
4.4.3.24.8 CEILING WORK 294
4.4.3.24.9 PLUMBING 296
4.4.3.24.10 BUILT-UP ROOFING 314
4.4.3.24.11 CARPENTRY WORK 316
4.4.3.24.12 BUILDING APPLIANCES & SPECIALTIES 318
0310297
Revision 0 Part 4.4 - i PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
BOOK III
PART 4.4. Civil Works 4.4.3 Technical Specification
4.4.3.24.1        SCOPE OF WORK
Miscellaneous Architectural Work shall include Bidder's designing, detailing, furnishing, installing inspection and testing of the following work covered by this specification and as applicable to Bidder's building work refers to "Summary of Work" and Technical Specification refers to "General Civil and Architectural Design Requirements". All materials and workmanship shall be neat and in accordance with the best modern practice and subject to prior approval of the Owner.
DOORS
- Hollow metal doors
- Rolling steel doors
- Aluminum doors
WINDOWS
- Aluminum top hung
- Aluminum horizontal projected
- Aluminum fixed windows
LOUVERS
- Fixed louvers
FLOOR FINISH
- Monolithic finish
- Separate concrete floor finish
- Ceramic
MASONRY
- Brick work
- Thin set tiles
CEILING WORK
- Louvered grid ceiling
- Acoustic ceiling
PLUMBING
0310298
Revision 0 Part 4.4 - 270 PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
- Floor drains
- Roof drains
- Plumbing fixtures
BOOK III
PART 4.4. Civil Works 4.4.3 Technical Specification
BUILT-UP ROOFING CARPENTRY WORK BUILDING APPLIANCES
- Kitchen unit.
- Steel lockers
4.4.3.24.2 CODES AND STANDARDS
The codes and standards of the following organizations extracted from "Codes and Standards" are specifically applicable to the design, manufacture and testing of the work included in this Specification:
AA Aluminum Association, U.S.A
AAMA Architectural Aluminum Manufacturers Association, U.S.A.
AC I American Concrete Institute
AMCA Air Movement and Control Association, Inc. U.S.A.
ANSI American National Standards Institute Inc.
ASTM American Society for Testing and Materials
AWWA American Water Works Association
LIA Lead Industries Association, Inc. U.S.A
JIS Japan Industrial Standard
NAAMM National Association of Architectural Metal Manufacturers,
U.S.A
. NEMA National Electrical Manufacturers Association, U.S.A
NFPA National Fire Protection Association, U.S.A
SSPC Steel Structures Painting Council, U.S.A.
UL Underwriters Laboratories, U.S.A
N.1.5. Peraturan     Konstruksi     Kayu     Indonesia     (Indonesian
Regulation for Wooden Structure)
N.J.10. Bata    Merah    sebagai     BahanBangunan     (Indonesian
Standard for Bricks)
IEC International Electrotechnical Commission
4.4.3.24.3 DOORS
GENERAL
All doors shall be designed and provided by Bidder and meet the following minimum requirements:
DESIGN LOAD Wind Load
Exterior doors shall be designed to withstand a minimum wind pressure of 150 kg/m2 and interior doors 100 kg/m2, uniformly applied over the entire
0310299
Revision 0 Part 4.4 - 271 PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
BOOK III
PART 4.4. Civil Works 4.4.3 Technical Specification
area of the door. The maximum deflection of the door under wind pressure loading shall be 1/120 of the width span.
Operating Load
All exterior doors shall be designed to operate under a minimum of 50-kg/m2 load uniformly applied over the entire area of the door.
SWING HOLLOW METAL DOORS HOLLOW METAL DOOR USAGE Class I Doors
Seamless hollow steel construction, with 1.5875 mm face sheets and additional tubular reinforcement at head, hinged jamb and locksets or push-pulls and prepared for surface hinges and through belted to door, unless otherwise indicated.
Class I doors shall be used for all exterior door locations. Class I doors shall also be used for interior doors that are exposed to heavy traffic areas, doors that are exposed to abusive usage or doors that are exposed to extreme difference in room pressure.
Class II Doors
Seamless hollow steel construction, with 1.27 mm face sheets and additional channel reinforcement at head and prepared for mortise hinges, unless otherwise indicated. Class II doors shall be used for all interior door locations.
HOLLOW METAL DOOR TYPE
The doors shall be flush type. Vision light shall be used when desired for a safety reason or required for a plant operating reason i.e. to view what is on the opposite side of the door when the door is in the closed position.
MATERIALS
Face sheets shall be roller-leveled or stretcher-leveled prime quality cold-rolled carbon steel.
Stiffeners, reinforcing and other accessories shall be prime quality carbon steel.
Glazing
a. Glazing shall conform to the applicable requirements of ANSI Z97.1.
b. Normal door glass shall consist of minimum 6 mm thick clear
polished wire reinforced glass.